Reasonable price Power Plant Seawater Electrolysis System - MGPS Seawater Electrolysis Online Chlorination System – Jietong Water Treatment
Reasonable price Power Plant Seawater Electrolysis System - MGPS Seawater Electrolysis Online Chlorination System – Jietong Water Treatment Detail:
Explanation
Seawater electrolysis chlorination system take use of natural seawater to produce on-line sodium hypochlorite solution with concentration 2000ppm by seawater electrolysis, which can effectively prevent the growth of organic matter on the equipment. The sodium hypochlorite solution is directly dosed to sea water through the metering pump, effectively control the growth of the sea water microorganisms, shellfish and other biological. and is widely used in the coastal industry. This system can meet the seawater sterilization treatment of less than 1 million tons per hour. The process reduces potential safety hazards related to the transportation, storage, transportation and disposal of chlorine gas.
This system has been widely used in large power plants, LNG receiving stations, seawater desalination plants, nuclear power plants, and seawater swimming pools.
Reaction Principle
First the seawater passes through the seawater filter, and then flow rate is adjusted to enter the electrolytic cell, and direct current is supplied to the cell. The following chemical reactions occur in the electrolytic cell:
Anode reaction:
Cl¯ → Cl2 + 2e
Cathode reaction:
2H2O + 2e → 2OH¯ + H2
Total reaction equation:
NaCl + H2O → NaClO + H2
The generated sodium hypochlorite solution enters the sodium hypochlorite solution storage tank. A hydrogen separation device is provided above the storage tank. The hydrogen gas is diluted below the explosion limit by an explosion-proof fan and is emptied. The sodium hypochlorite solution is dosed to the dosing point through the dosing pump to achieve sterilization.
Process flow
Seawater pump → Disc filter → Electrolytic cell → Sodium hypochlorite storage tank → Metering dosing pump
Application
● Seawater Desalination Plant
● Nuclear power station
● Sea Water Swimming Pool
● Vessel/Ship
● Coastal thermal power plant
● LNG Terminal
Reference Parameters
Model |
Chlorine (g/h) |
Active Chlorine Concentration (mg/L) |
Seawater flow rate (m³/h) |
Cooling water treatment capacity (m³/h) |
DC Power consumption (kWh/d) |
JTWL-S1000 |
1000 |
1000 |
1 |
1000 |
≤96 |
JTWL-S2000 |
2000 |
1000 |
2 |
2000 |
≤192 |
JTWL-S5000 |
5000 |
1000 |
5 |
5000 |
≤480 |
JTWL-S7000 |
7000 |
1000 |
7 |
7000 |
≤672 |
JTWL-S10000 |
10000 |
1000-2000 |
5-10 |
10000 |
≤960 |
JTWL-S15000 |
15000 |
1000-2000 |
7.5-15 |
15000 |
≤1440 |
JTWL-S50000 |
50000 |
1000-2000 |
25-50 |
50000 |
≤4800 |
JTWL-S100000 |
100000 |
1000-2000 |
50-100 |
100000 |
≤9600 |
Project Case
MGPS Seawater Electrolysis online Chlorination System
6kg/hr for Korea Aquarium
MGPS Seawater Electrolysis online Chlorination System
72kg/hr for Cuba power plant
Product detail pictures:
Related Product Guide:
We support our prospective buyers with ideal top quality merchandise and superior level provider. Becoming the specialist manufacturer in this sector, we have now attained abundant practical expertise in producing and managing for Reasonable price Power Plant Seawater Electrolysis System - MGPS Seawater Electrolysis Online Chlorination System – Jietong Water Treatment , The product will supply to all over the world, such as: Jamaica, Houston, Spain, Really should any of these items be of interest to you, please let us know. We will be pleased to give you a quotation upon receipt of one's detailed specifications. We've our personal specialist R&D enginners to meet any of the requriements, We look forward to receiving your enquires soon and hope to have the chance to work together with you inside the future. Welcome to take a look at our organization.
By Mike from Burundi - 2017.08.21 14:13
High Quality, High Efficiency, Creative and Integrity, worth having long-term cooperation! Looking forward to the future cooperation!
By Dana from Senegal - 2018.11.06 10:04